Rixen Messtechnik MU-Analog-65 Ringbalance Differential Pressure Transmitter
Roll over image to zoom in
  • Exclusive UK and Ireland Rixen Messtechnik representative
  • Guidance selecting the correct low-pressure range
  • 4-wire and 2-wire configuration guidance

Rixen Messtechnik MU-Analog-65 Ringbalance Differential Pressure Transmitter

Analogue scale Ringbalance transmitter for low draft, pressure and differential pressure measurement, available in 4-wire or 2-wire loop-powered versions.

Key highlights

  • Analogue transmitter: Large scale display with electrical signal output
  • 4-wire version: 0–20 mA, 4–20 mA and 0–10 V outputs as standard
  • 2-wire version: Loop-powered 4–20 mA output option
  • Low-pressure ranges: Configurable for draft, pressure and differential pressure duties
  • Local indication: 150 x 150 mm scale remains readable at the instrument
  • Factory calibrated: Factory calibration certificate included

The Rixen Messtechnik MU-Analog-65 is a Ringbalance differential pressure transmitter with a large analogue scale for low draft, pressure and differential pressure measurement. It is designed for applications where local visual indication and remote signal transmission are both required.

Using Rixen Messtechnik’s mechanical Ringbalance measuring principle, the MU-Analog-65 combines a mechanical low-pressure measuring system with electrical output signals for control or monitoring systems. The standard 4-wire version provides 0–20 mA, 4–20 mA and 0–10 V outputs.

The same product family includes the MU-Analog-65-2L loop-powered version, which provides a passive 4–20 mA output using a 2-wire connection. This version is suitable where a simpler loop-powered signal is preferred, including retrofit or control-system integration applications.

The MU-Analog-65 range is suited to low-pressure industrial gas and air applications such as cleanroom pressure monitoring, ventilation systems, HVAC plant, furnace pressure indication and general differential pressure monitoring. The 150 x 150 mm analogue scale provides clear local indication while the transmitter output supports external system connection.

Measuring range, scale unit, output version and supply arrangement are selected at order. Available units include Pa, kPa, daPa, mbar, mmWS, mmCE and in.W.C., while DZ overload protection can be considered where pressure spikes or abnormal overload conditions may occur.

Key Features

  • Analogue Ringbalance transmitter: Combines local analogue indication with transmitter output for low draft, pressure and differential pressure measurement.
  • Large scale display: 150 x 150 mm analogue scale supports clear local reading during operation, commissioning and maintenance checks.
  • Standard 4-wire output version: MU-Analog-65 provides 0–20 mA, 4–20 mA and 0–10 V outputs for BMS, SCADA and building automation integration.
  • Passive 2-wire loop-powered version: MU-Analog-65-2L provides a 4–20 mA passive output where reduced wiring or retrofit installation is preferred.
  • Configurable low-pressure range: Measuring range is selected to suit the application, with available ranges from 0…40 Pa to 0…1.8 kPa.
  • Selectable scale units: Units include Pa, kPa, daPa, mbar, mmWS, mmCE and in.W.C. to align with site or project requirements.
  • IP65 wall-mounted housing: Glass-reinforced polycarbonate housing with hardened front glass supports industrial installation environments.
  • Overload protection option: DZ overload protection can be specified where pressure spikes or abnormal overload conditions may exceed standard limits.

Specifications

Measurement
Product TypeRingbalance differential pressure transmitter with analogue display
ModelsMU-Analog-65 4-wire version; MU-Analog-65-2L 2-wire version
Measuring PrincipleRingbalance principle
Measuring PickupMagnetic field sensor
Measurement DutiesDraft, pressure and differential pressure
DisplayLarge analogue display, 150 x 150 mm
AccuracyMaximum error ±1.5% of span, or ±1.5 Pa
Ambient Temperature0 °C to +50 °C (32 °F to 122 °F)
Measuring Range and Scale
Measuring Range0…40 Pa to 0…1.8 kPa (0.15″ W.C. to 7″ W.C.)
Example Pressure, Draft and Differential Pressure Ranges0…40 Pa, 0…50 Pa, 0…60 Pa, 0…80 Pa, 0…100 Pa, 0…150 Pa, 0…200 Pa, 0…250 Pa, 0…300 Pa, 0…500 Pa, 0…600 Pa, 0…700 Pa, 0…800 Pa, 0…1,000 Pa, 0…1,200 Pa, 0…1,500 Pa, 0…1,800 Pa
Example Pressure / Draft Ranges-20…0…+20 Pa, -25…0…+25 Pa, -50…0…+50 Pa, -100…0…+100 Pa, -250…0…+250 Pa, -500…0…+500 Pa, -10…0…+40 Pa, -40…0…+10 Pa, -30…0…+10 Pa, -10…0…+30 Pa, -20…0…+80 Pa, -80…0…+20 Pa
Scale UnitsPa, kPa, daPa, mbar, mmWS, mmCE, in.W.C.
Outputs and Supply
MU-Analog-65 Output Signals0–20 mA, 4–20 mA and 0–10 V
MU-Analog-65 Maximum Load680 Ohm for mA outputs; minimum 2 kOhm for voltage output
MU-Analog-65 Power Supply230 VAC; also available with 24, 110, 120 or 240 VAC; 24 VDC at additional price
MU-Analog-65-2L Output Signal4–20 mA
MU-Analog-65-2L Power Supply24 VDC (12–28 V DC)
MU-Analog-65-2L Maximum Load600 Ohm at 24 V DC
Housing and Mounting
HousingWall-mounted IP65 housing
Housing MaterialGlass-reinforced polycarbonate, light grey
Front PaneHardened front glass pane
MountingThrough inner screw channels or using the attached mounting frame
Cable FittingPG9 with strain relief
Filling Fluids and Overload Protection
Filling FluidFactory-filled. The type of oil does not need to be stated in the order.
Mineral OilDensity 0.8 kg/l; for ranges up to ±700 Pa; maximum overload ±900 Pa
Synthetic OilDensity 1.9 kg/l; for ranges over ±700 Pa; maximum overload ±2.1 kPa
Overload ProtectionDZ overload protection device available as an option where 900 Pa / 2.1 kPa limits may be exceeded
Compliance and Ordering
EMCAccording to EN50081-2 (Emission) and EN50082-2 (Immunity)
TypesMU-Analog-65 4-wire version; MU-Analog-65-2L 2-wire version
Required Order InformationType, measuring range and power supply
CalibrationFactory calibration certificate included

Support

Able Instruments are Rixen Messtechnik’s Exclusive Representative for Sales and Service in the UK and Ireland, providing application and configuration support for analogue low-pressure transmitter applications.

  • Application guidance: Advice on whether the MU-Analog-65 is suitable for the required draft, pressure or differential pressure measurement duty
  • Version selection: Support choosing between the 4-wire MU-Analog-65 and the 2-wire loop-powered MU-Analog-65-2L
  • Range selection: Guidance selecting the correct low-pressure range and scale unit for the application
  • Output and supply selection: Support confirming signal output, supply voltage and control system integration requirements
  • Overload protection: Advice on whether DZ overload protection should be considered where pressure spikes may occur
  • Exclusive UK and Ireland Rixen Messtechnik representative
  • Guidance selecting the correct low-pressure range
  • 4-wire and 2-wire configuration guidance
Summary