Rixen Messtechnik Rixotact_4 Ringbalance Differential Pressure Controller
Roll over image to zoom in
  • Exclusive UK and Ireland Rixen Messtechnik representative
  • Guidance selecting the correct low-pressure range
  • Controller and setpoint configuration guidance

Rixen Messtechnik Rixotact_4 Ringbalance Differential Pressure Controller

Ringbalance differential pressure controller for low draft, pressure and differential pressure measurement with integrated three-point step control.

Key highlights

  • Integrated controller: Three-point step control with PD action
  • Low-pressure measurement: Configurable for draft, pressure and differential pressure duties
  • 0–10 V output: Transmitter signal proportional to the measured actual value
  • Adjustable setpoints: Two setpoints adjustable from 20% to 80% of span
  • Control settings: Proportional band, differential action, deadband and switching frequency
  • Factory calibrated: Factory calibration certificate supplied with each unit

The Rixen Messtechnik Rixotact_4 is a Ringbalance differential pressure controller for measuring low draft, pressure and differential pressure. It is designed for applications where the measured pressure value is also used for automatic control.

Using Rixen Messtechnik’s Ringbalance measuring principle, the Rixotact_4 combines low-pressure measurement with an integrated three-point step controller. This makes it suitable where relay-based open, close or hold control is required for pressure-related process or ventilation duties.

The controller includes two selectable setpoints, adjustable from 20% to 80% of span and selected via terminals. Control settings include proportional band, differential action, neutral zone and switching frequency, allowing the instrument to be configured around the control behaviour required by the application.

In addition to the controller function, the Rixotact_4 provides a 0–10 V transmitter output proportional to the measured actual value. The LCD display can show either the actual value or the selected setpoint, supporting commissioning, checking and adjustment at the instrument.

The Rixotact_4 is suited to low-pressure control applications such as furnace pressure control, ventilation control, room pressure control and similar industrial gas and air duties. Measuring range, power supply and overload protection requirements should be reviewed before ordering.

Key Features

  • Ringbalance pressure controller: Combines low draft, pressure and differential pressure measurement with integrated three-point step control.
  • Three-point step control: Provides PD action for applications requiring open, close or hold control behaviour.
  • Selectable setpoints: Two setpoints, W1 and W2, are adjustable from 20% to 80% of span and selectable via terminals.
  • Configurable control response: Proportional band, differential action, neutral zone and switching frequency can be adjusted to suit the application.
  • 0–10 V transmitter output: Provides a signal proportional to the measured actual value for external monitoring or signal use.
  • LCD local display: 3½-digit LCD display can show the actual value or selected setpoint for commissioning and local checking.
  • Configurable low-pressure range: Measuring range can be selected from 0…40 Pa to 0…1.8 kPa, including ranges within these limits.
  • Overload protection option: DZ overload protection can be specified where pressure spikes or abnormal overload conditions may exceed standard limits.

Specifications

Measurement
Product TypeRingbalance differential pressure controller with transmitter output
ModelRixotact_4
Measuring PrincipleRingbalance measuring principle
Measuring PickupHall sensor / magnetic-field sensor
Measurement DutiesDraft, pressure and differential pressure
DisplayLCD, 3½ digit, 12.5 mm character height
AccuracyMaximum error ±1.5% of span, or ±1.5 Pa
Ambient Temperature0 °C to +50 °C (32 °F to 122 °F)
Measuring Range and Units
Measuring Range0…40 Pa to 0…1.8 kPa (0.15″ W.C. to 7″ W.C.), and any range within these limits
Example Pressure, Draft and Differential Pressure Ranges0…40 Pa, 0…50 Pa, 0…60 Pa, 0…80 Pa, 0…100 Pa, 0…150 Pa, 0…200 Pa, 0…250 Pa, 0…300 Pa, 0…500 Pa, 0…600 Pa, 0…700 Pa, 0…800 Pa, 0…1,000 Pa, 0…1,200 Pa, 0…1,500 Pa, 0…1,800 Pa
Example Pressure / Draft Ranges-20…0…+20 Pa, -25…0…+25 Pa, -50…0…+50 Pa, -100…0…+100 Pa, -250…0…+250 Pa, -500…0…+500 Pa, -10…0…+40 Pa, -40…0…+10 Pa, -30…0…+10 Pa, -10…0…+30 Pa, -20…0…+80 Pa, -80…0…+20 Pa
UnitsPa, kPa, daPa, mbar, mmW.C., in.W.C.
Controller
Controller TypeThree-point step controller with PD action
SetpointsW1 / W2, two setpoints adjustable from 20% to 80% of span
Setpoint SelectionSelectable via terminals 3–4
LCD SwitchUpper position shows actual value X; lower position shows actual setpoint W
Control OutputsPotential-free relay contacts
Relay Contact Rating250 V / 2 A
Control SettingsP proportional band, D differential action, NZ neutral zone / deadband, F switching frequency
Transmitter and Supply
Transmitter Output0–10 V, proportional to the measured actual value X
Minimum Load2 kOhm
Power Supply230 V AC; also available with 110, 120 or 240 V AC, or 24 V DC
Power Consumption3.5 VA
Housing and Mounting
Protection RatingIP65
HousingWall-mounted housing, glass-reinforced polycarbonate, light grey
Front PaneHardened front glass pane
Dimensions180 x 255 x 165 mm
MountingThrough inner screw channels or using the attached mounting frame
Cable FittingPG9 with strain relief
Filling Fluids and Overload Protection
Filling FluidFactory-filled. The type of oil does not need to be stated in the order.
Mineral OilDensity 0.8 kg/l; for ranges up to ±700 Pa; maximum overload ±900 Pa
Galden Synthetic OilDensity 1.9 kg/l; for ranges over ±700 Pa; maximum overload ±2.1 kPa
Overload ProtectionDZ overload protection device available as an option where overload limits may be exceeded
Compliance and Ordering
EMCAccording to EN50081-2 (Emission) and EN50082-2 (Immunity)
Required Order InformationType, measuring range, power supply and options
Range Selection NoteFor best results, select a range so estimated setpoints lie approximately in the middle third of the measuring range
CalibrationFactory calibration certificate supplied to each unit

Support

Able Instruments are Rixen Messtechnik’s Exclusive Representative for Sales and Service in the UK and Ireland, providing application and configuration support for low-pressure control applications.

  • Application guidance: Advice on whether the Rixotact_4 is suitable for the required draft, pressure or differential pressure control duty
  • Range selection: Support selecting a measuring range so expected setpoints sit appropriately within the span
  • Controller configuration: Guidance on setpoints, deadband and three-point step control requirements
  • Output and supply selection: Support confirming the 0–10 V transmitter output and power supply requirements
  • Overload protection: Advice on whether DZ overload protection should be considered where pressure spikes may occur
  • Exclusive UK and Ireland Rixen Messtechnik representative
  • Guidance selecting the correct low-pressure range
  • Controller and setpoint configuration guidance
Summary
Contact

Prefer to speak to a Product Specialist? Call us on:
01189311188